AdsorbAIR pressurization units are designed to maintain a G1 reactivity level within corrosive rooms, as defined by ANSI/ISA Standard S71.04-2013. In addition to AdsorbAIR, RecircAIR recirculation units are recommended for spaces that have high traffic levels, very dusty environments, or are critical to overall plant operation. The addition of recirculation allows reduced recovery times for increased contaminant levels due to entry into the pressurized space. The activated carbon media oxidizes airborne contaminants, breaking them down to harmless components.
Advance Industrial Refrigeration provides full mechanical turnkey solutions for corrosion control within electrical room environments, including air conditioners, pressurization units, corrosion monitoring, installation and maintenance.
Key Features
Capacities of 1000 and 2000 CFM
Welded stainless steel frame structure
16 gauge 304 stainless steel exterior casing
Hinged access doors to fan and filter sections
Fan(s) with aluminum backward inclined wheels
Pre-filters: o 2” - MERV 8 o 6” – MERV 14
Activated carbon modules
Post-filters: o 2” - MERV 8 o 6” – MERV 14
Low filter velocities - 250 fpm
Local pressure gauges for each filter section
ECM motor for adjustable fan capacity
Single point 240V/1Ph/60Hz power